Emergency break glass Fire Alarm manual call point

  • Model: HM-911
  • Shipping Weight: 0.3 kgs
  • 200 Units in Stock

 Ask a Question 

$8.50

Add to Cart:
Conventional Manual Call Point, Operates by Advanced MCU Expert Algorithm Software.
They work perfectly with all conventional intelligent fire control panels
Technical Specifications
Ordering Information
Individual(1 units)
Dimensions
(w x d x h millimetres)
86x86x45
Weight: 150g
Operating Temperature Range: -10°C to 50°C
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Latching Alarm: Reset by momentary power interruption
Top Side
Figure 1. Dimension of manual call point:
Electrical Ratings
System Voltage (nominal): 24 VDC (9V~ 28VDC)
Standby Current: 60 μA @ 24VDC
Alarm Current: 10~30 mA @ 24VDC

call-point based upon our industry standard series housing, and features easy to install, push-fit wiring terminals.
The unit can support either a 'Frangible Glass' element or a 'Non Frangible Plastic' element.
Push in and Pull Down Call Point
Can be reset by key
Red colour
Fire proof materials
470 Ohm Resistance
Modern style Call Point

Copyright © 2026 Vedard Security Alarm Systems. Powered by Vedard Security Alarm Technology